Phase
Conductor Temp
Ambient Temp
Trip Curve
Load Type
Quick Presets
✓
⚠️ Motor branch-circuit protection follows NEC Article 430, not the standard 125% rule. Starting current, service factor, and overload protection (separate from short-circuit/ground-fault protection) are not fully modeled here — verify with a licensed electrician and, for conductor sizing specifically, cross-check with the Motor Starting Current Estimator.
⚠️ HVAC/AC compressor protection per NEC 440.22 is sized from rated-load current (RLA), not locked-rotor amps (LRA). If a 175%-sized device trips on startup, NEC 440.22(A) Exception 1 permits sizing up to 225% of RLA — verify manufacturer nameplate maximum overcurrent protection (MOCP) if provided, which takes precedence.
⚠️ NEC 310.10(H) permits paralleling conductors 1/0 AWG and larger only, with all sets identical in length, material, size, insulation, and terminations. The size selected here is smaller than that — verify with a licensed electrician before paralleling.
Results
Recommended Breaker
—
A
Paired Min. Wire
—
Wire Ampacity
—
A
Load Current
—
A
Breaker Rating Used—
Formula: —
Standard Breaker Sizes — Utilization

Each bar is a standard breaker size, and the height is how much of that breaker's rating the adjusted load uses. The size this page recommends is marked in gold. The dashed line is 100 percent of the rating.

Neighboring Sizes Recommended Size 100% Capacity
Breaker size comparison chart.

Results are engineering estimates based on published NEC standard breaker sizes (240.6(A)), NEC Table 310.16 general conductor ampacity, NEC Table 310.15(B)(1) ambient-temperature correction factors, NEC 240.4(D) small-conductor limits, and NEC Table 430.248/430.250 motor full-load current values (cross-checked against independent published reproductions). The breaker size still has to be checked against the installation and the adopted edition of the National Electrical Code (NFPA 70). Verify with a licensed electrician before any electrical work.