Pick a calculation mode, set the circuit parameters, and click Calculate. The breaker must clear its own sizing rule and the paired conductor must have adequate ampacity.
Percent of rated capacity used by your (continuous-adjusted) load across neighboring standard breaker sizes. Your recommended size is highlighted in gold; the dashed line marks 100% capacity.
Results are engineering estimates based on published NEC standard breaker sizes (240.6(A)), NEC Table 310.16 general conductor ampacity, NEC Table 310.15(B)(1) ambient-temperature correction factors, NEC 240.4(D) small-conductor limits, and NEC Table 430.248/430.250 motor full-load current values (cross-checked against independent published reproductions). Actual sizing varies with installation conditions and the adopted NEC edition. Verify with a licensed electrician before any electrical work.
NEC 240.6(A) standard breaker/fuse sizes, with the minimum paired 75°C copper conductor (before ambient derating or the 240.4(D) small-conductor cap).
| Standard Breaker | Min. Copper (75°C) |
|---|
General ampacity per NEC Table 310.16, 30°C ambient, not more than 3 current-carrying conductors. Verify with a licensed electrician for your actual installation.
NEC 240.4(D) Small-Conductor Overcurrent Protection Caps — these conductors are capped at a maximum breaker/fuse rating regardless of their table ampacity, to protect terminations.
| Size | Copper Cap | Aluminum Cap |
|---|
Four real-world scenarios, one per mode. Click "Load This Example" to run it in the calculator above.
The 100% / 125% rule (standard loads)
NEC 210.20(A) and 240.6(A) require a breaker sized at 100% of a non-continuous load, or 125% of a continuous load (one expected to run at maximum current for three hours or more), rounded up to the next standard breaker size. The same 125% factor applies to the paired conductor's required ampacity.
Motor circuits are sized by percentage of full-load current, not the 125% rule
NEC Article 430, specifically Table 430.52, sizes motor branch-circuit short-circuit and ground-fault protection as a percentage of the motor's full-load current (FLC) from NEC Table 430.248 (single-phase) or 430.250 (three-phase) — not nameplate current. Typical maximums are 250% for an inverse-time breaker, 175% for a time-delay fuse, 300% for a non-time-delay fuse, and up to 800% for an instantaneous-trip breaker (motor circuit protector only). This headroom accommodates motor starting (inrush) current, which can be 6–8× running current for a few cycles. Motor overload protection — protecting the motor itself from sustained overload — is a separate NEC 430 Part III requirement not modeled by this calculator.
HVAC/AC compressor sizing (NEC 440.22)
Air-conditioning and refrigeration compressor branch-circuit protection is sized from the rated-load current (RLA) or branch-circuit selection current, not locked-rotor amps (LRA), at up to 175% under NEC 440.22(A). If this trips on startup, NEC 440.22(A) Exception 1 permits an increase up to 225% of that same current. Manufacturer nameplate "Maximum Overcurrent Protection" (MOCP), when provided, takes precedence over a calculated value.
Ambient temperature derating
NEC Table 310.15(B)(1) publishes correction factors for conductor ampacity when the ambient air temperature exceeds the 30°C (86°F) baseline used in the base ampacity tables. Higher ambient temperature reduces a conductor's usable ampacity — a wire that comfortably carries a load at 30°C may not be adequate in a hot attic or rooftop conduit run without upsizing.
AFCI and GFCI requirements
NEC 210.12 requires arc-fault circuit-interrupter (AFCI) protection on most 120V, 15A and 20A branch circuits supplying outlets in dwelling-unit living areas, bedrooms, and similar rooms. NEC 210.8 requires ground-fault circuit-interrupter (GFCI) protection in kitchens, bathrooms, garages, outdoor locations, unfinished basements, crawl spaces, and laundry areas. Some locations require both protections, available as a combination AFCI/GFCI breaker. Local amendments can expand these requirements beyond the base NEC — this calculator's flag is a starting point, not a final determination.
Parallel conductors and the breaker
NEC 310.10(H) permits paralleling conductors 1/0 AWG and larger, with every parallel set matching in length, material, size, insulation, and terminations. Paralleling changes the conductor arrangement, not the overcurrent-protection sizing math — the breaker is still sized from the total load using the standard rule. What must be separately verified is that the combined ampacity of all parallel sets meets or exceeds that breaker rating.
Trip curves (B/C/D)
Trip curve is an IEC 60898 classification, common on international/DIN-rail breakers, describing the multiple of rated current at which the instantaneous magnetic trip operates: roughly 3–5× for Curve B (resistive loads), 5–10× for Curve C (general/mixed loads, small motors), and 10–20× for Curve D (transformers, capacitor banks, high-inrush motors). Standard North American thermal-magnetic breakers don't typically publish a curve letter in the same way, so this selector is most relevant for installations using IEC-style equipment or side-by-side comparison.