Standard
Phase
Conductor Temp
Conduit Type
Load Type
Quick Presets
✓
⚠️ Motor-load calculation (horsepower input): motor starting current, efficiency, service factor, and NEC Article 430 requirements are not modeled by this estimate. Use the Motor Starting Current Estimator and have a licensed electrician verify conductor sizing for any motor circuit.
⚠️ NEC 310.10(H) permits paralleling conductors 1/0 AWG (or 50 mm² in IEC) and larger only, with all sets identical in length, material, size, insulation, and terminations. The size selected here is smaller than that — verify with a licensed electrician before paralleling.
Results
Recommended Size
—
Percent Drop
—
%
Ampacity Rating
—
A
Load Current
—
A
Ampacity Used—
Formula: —
Wire-Size Comparison

Each bar is the percent drop for a neighboring conductor on the circuit you entered, shown beside the ampacity result. The size this page selected is marked in gold. The dashed line is the 3 percent branch-circuit mark. Use it to see whether a larger conductor is needed for the length of the run, not only for ampacity.

Neighboring Sizes Your Size 3% NEC Recommendation
Wire-size comparison chart.

Results are engineering estimates based on published NEC Table 310.16 general ampacity (30°C ambient, ≤3 current-carrying conductors) and conductor resistance and reactance at the selected operating temperature and conduit type. Actual ampacity and voltage drop vary with installation conditions. Verify with a licensed electrician before any electrical work.