Choose Residential or Commercial, select the voltage system, enter the load details, and click Calculate. Both modes work standalone or together with the phase/leg balance section below.
Each bar is a standard load-center rating, and the height is how much of that rating the demand plus spare space uses. The size this page recommends is marked in gold. The dashed line is 100 percent of the rating.
Add individual circuits below and assign each to a leg or phase — this works together with the mode above using the same voltage system selection. Runs automatically as part of Calculate.
Add circuits above, then click Calculate, to see leg/phase balance.
Results are engineering estimates based on published NEC Article 220 formulas and demand-factor tables (220.12, 220.42, 220.52, 220.53, 220.54, 220.55, 220.56, 220.60, 220.14(I)) and NEC 430.24. Several simplifications are disclosed in the Comprehensive Guide below. The panel size still has to be checked against the installation and the adopted edition of the National Electrical Code (NFPA 70). Verify with a licensed electrician before any electrical work.