Fill Standard

Conductors
✓
⚠️ Jam probability flag: with exactly three conductors of the same size, a conduit-ID-to-cable-OD ratio between 2.8 and 3.2 can cause jamming during the pull (NEC Chapter 9, Table 1, Informational Note No. 2). Consider a different conduit size or conductor arrangement.
ℹ️ Utility fill standard selected: a flat 40% maximum is applied regardless of conductor count. This is a common utility-company practice, not a requirement of the National Electrical Code (NFPA 70) — confirm the exact standard with the utility for utility-owned conduit.
Results
Fill Percentage
—
%
Conduit Size
—
Total Conductor Area
—
in²
Max Allowed Area
—
in²
Conduit Fill Used—
Formula: —
Area Composition

Total conductor area compared against the maximum allowed fill area and the conduit's full internal area for the selected size.

Conductor Area Max Allowed Area Conduit Total Area
Conduit fill area comparison chart.
All Trade Sizes — EMT

Fill percentage for your current conductor set across every trade size of the selected conduit type. The size matching your Conduit Trade Size selection is highlighted.

Trade SizeTotal AreaMax Allowed AreaFill %Status

Results are engineering estimates based on published NEC Chapter 9 fill percentages (Table 1), conduit internal areas (Table 4), and conductor areas (Table 5). Conduit area values are provided for EMT, PVC Schedule 40/80, RMC, and IMC and have been cross-checked against independent published reproductions — FMC, LFMC, and LFNC-B are not yet included pending verification. Actual sizing varies with installation conditions and the adopted edition of the National Electrical Code (NFPA 70). Verify with a licensed electrician before any electrical work.

Estimates pulling tension and sidewall pressure using standard NECA-published formulas. Conductor weight is auto-filled from the main calculator above (editable).

Bend Input

300 lb/ft is a commonly published general limit — override if your cable's manufacturer spec lists a different value.

✓
Pulling Tension
—
lb
Max Allowable Tension
—
lb
Sidewall Pressure
—
lb/ft
Formula: —

Results are estimates using standard NECA-published pulling formulas (T = W × L × f for a straight pull; the capstan equation T₂ = T₁ × e^(f·θ) for bends; sidewall pressure SWP = T ÷ R). Actual safe pulling tension depends on lubricant, exact cable jacket/construction, and real installation geometry — verify against the cable manufacturer's published maximum tension and sidewall pressure rating before pulling.

MV cable outer diameter varies by manufacturer and construction. Typical diameters shown are estimates from NEC Article 315.10(B) minimum insulation levels — use Custom OD for an exact product.

✓
Fill Percentage
—
%
Total Conductor Area
—
in²
Max Allowed Area
—
in²

Typical MV cable diameters are estimates derived from NEC Article 315.10(B) minimum insulation-thickness levels by voltage class, not any specific manufacturer's product. Actual cable OD varies with shielding and jacket construction. Enter the exact OD from the cable's spec sheet using the field above for an installation-ready result.